Four digit Meters
The EX-R series incorporates separate voltage and
current meters on each main output with a resolution of 10mV and 1mA (EX355R and EX354RD/T) or 10mA (EX1810R/2020R/4210R).
The fixed resolution avoids the misinterpretation of
readings that can occur with auto-ranging 3 or 3½ digit meters where the
decimal point position moves as the reading changes.
|
|
|
|
 |
Remote Sensing
Each main output incorporates remote sense terminals
that can be enabled or disabled at the flick of a switch.
Remote sensing is essential for maintaining precise regulation at the
load and true metering of the load voltage. Many other power supplies
omit remote sense, and quote regulation figures that could never be
achieved in practice. |
|
|
|
|
|
An Example
A 2 metre length of a 24/0.2 wire pair has a
resistance of around 0.1 Ohms. For a 5V load drawing 3A the metering error
without remote sense would be 0.3V and the effective full current load
regulation would be around 6%, against a quoted figure of perhaps 0.01%
for the power supply itself. |
|
|
|
 |
Simplicity in use
EX-R series power supplies use classic analog
controls for voltage and current.
The large and bright displays have a fixed
resolution to avoid confusion.
Preset voltage and current levels are shown when the DC output switch is
turned off.
Remote sense is available when needed but is disabled by setting the
switch to Local. |
|
|
|
 |
|
Thurlby Thandar Instruments
Limited
Glebe Road, Huntingdon, Cambridgeshire PE29 7DR United Kingdom
Tel: +44 1480 412451 Fax: +44 1480
450409 Web: www.tti-test.com Email:
sales@tti-test.com |
 |
| |
|
|
|
|